J063--Fire Alarm Service and Upgrade
- Country
- United States
- Published
- February 2, 2026
- Deadline
- February 4, 2026
Description
{"description":"The purpose of this amendment is to answer questions submitted by interested vendors. \n\nThe period for questions remains closed\n\nPlease see responses to vendor questions below: \n\nQuestion: What is the fire alarm device count by building for each location?\nAnswer: \nManhattan:\nBuilding #1 Main: 518 devices\nBuilding #2 Engineering: 7 devices\nBuilding #3 HR: 18 devices\nBuilding #5 AC Plant: 9 devices\nBuilding #6 OPC: 105 devices\n\nSt. Albans: \nBuilding #60 3 devices\nBuilding #64 10 devices\n*Building #65 11 devices\nBuilding #85 77 devices\nBuilding #86 75 devices\nBuilding #87 76 devices\nBuilding #88 76 devices\nBuilding #89 160 devices\nBuilding #91 55 devices\nBuilding #92 31 devices\nBuilding #93 30 devices\nBuilding #173 19 devices\nBuilding #176 5 devices \n\nBrooklyn: \nBuilding #1 Main: Engineering 659 devices\nBuilding#2 Domiciliary: 66 devices\nBuilding #4 Engineering:  33 devices\nBuilding #6 Chapel: 6 devices\nBuilding #8 Linear Accelerator: 1 device\nBuilding #14 Regional Counsel/Data Center: 18 devices\nBuilding #15 OPC: 195 devices\nBuilding #16 Daycare: 10 devices\n\nQuestion: What is the total number of buildings included at each campus?\nAnswer: \nManhattan: \n5 Buildings \n\nSt. Albans:\n13 buildings *including building #65 which is initially bypassed, See Section VI.A.3. of the Scope. \n\nBrooklyn: \n8 Buildings \n\n\nQuestion: What are the manufacturers and model numbers for all fire alarm control panels\nAnswer: \nManhattan:\nManufacturer: Notifier by Honeywell (ONYX Series)\nModel(s) Identified from Panel Labels:\nONYX NFS2-3030D / NFS2-3030ND\nONYX NFS2-640(E) / NFS-320SYS(E)\n\nSt. Albans:\nEdwards EST-3\n\nBrooklyn: \nManufacturer: Notifier Pittway Company\nModel(s) Identified from Panel Labels:\nAFP-400W/CBC \nAM2020/AFP1010/CBC\n#System 5000W/CBC\nManufacturer: Honeywell\nModel(s) Identified from Panel Labels:\nAFO 300/AFP 400 CBC\nNFS2-640(E) / NFS 320SYS(E)\nNFS2-3030D\n\nQuestion: Will existing fire alarm system AutoCAD (.dwg files) be provided to the contractor for updating the schematic diagrams or will these drawings be required to be created from scratch?\nAnswer: Existing fire alarm as built drawings are available and will be provided to the contractor in AutoCAD (.dwg) format and shall be used as a baseline. These drawings may not reflect current system conditions. The contractor shall field verify existing conditions and update the drawings to reflect the current fire alarm system configuration. Building floor plans may also be available in AutoCAD (.dwg) format for use in preparing the updated fire alarm drawings.\n\nQuestion: Can you please confirm the base scope of work does not require the contractor to install new printers?\nAnswer: The VA will provide printers. Contractor must install and test. \nPlease see updated Schedule below. Line Items 0001AC, 0002AC, and 0003AD have been added.\n\nLine Item\nDescription\nQuantity\nUnit of Measure\nUnit Price\nTotal Price\n0001\nManhattan - Fire Alarm System\n0001AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n0001AB\nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n0001AC \nPrinter Installation and Testing\n2\nEA\n\n\n0002\nBrooklyn Fire Alarm System\n0002AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n0002AB \nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n0002AC \nPrinter Installation and Testing\n1\nEA\n\n\n0003\nSt. Albans Fire Alarm System\n0003AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n0003AB\nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n0003AC\nSystem Upgrade to Replace Edwards EST-3\n1\nJB\n\n\n0003AD\nPrinter Installation and Testing\n1\nEA\n\n\n0004\nLabor for Repairs at any Facility, regular working hours. (see SOW section I) \n1\nHR\n\n\n0005\nLabor for Repairs at any Facility, overtime working hours. (see SOW section I)\n1\nHR\n\n\n0006\nLabor for Repairs at any Facility, holiday working hours. (see SOW section I)\n1\nHR\n\n\n0007\nParts for Repairs at any Facility (see SOW section I)\n-\n-\n-\n-\nOPTION 1\n1001\nManhattan - Fire Alarm System\n1001AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n1001AB\nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n1002\nBrooklyn Fire Alarm System\n1002AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n1002AB \nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n1003\nSt. Albans Fire Alarm System\n1003AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n1003AB\nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n1004\nLabor for Repairs at any Facility, regular working hours. (see SOW section I) \n1\nHR\n\n\n1005\nLabor for Repairs at any Facility, overtime working hours. (see SOW section I)\n1\nHR\n\n\n1006\nLabor for Repairs at any Facility, holiday working hours. (see SOW section I)\n1\nHR\n\n\n1007\nParts for Repairs at any Facility (see SOW section I)\n-\n-\n-\n-\nOPTION 2\n2001\nManhattan - Fire Alarm System\n2001AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n2001AB\nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n2002\nBrooklyn Fire Alarm System\n2002AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n2002AB \nSemi-Annual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n2003\nSt. Albans Fire Alarm System\n2003AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n2003AB\nSemi-Annual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n2004\nLabor for Repairs at any Facility, regular working hours. (see SOW section I) \n1\nHR\n\n\n2005\nLabor for Repairs at any Facility, overtime working hours. (see SOW section I)\n1\nHR\n\n\n2006\nLabor for Repairs at any Facility, holiday working hours. (see SOW section I)\n1\nHR\n\n\n2007\nParts for Repairs at any Facility (see SOW section I)\n-\n-\n-\n-\nOPTION 3\n3001\nManhattan - Fire Alarm System\n3001AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n3001AB\nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n3002\nBrooklyn Fire Alarm System\n3002AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n3002AB \nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n3003\nSt. Albans Fire Alarm System\n3003AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n3003AB\nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n3004\nLabor for Repairs at any Facility, regular working hours. (see SOW section I) \n1\nHR\n\n\n3005\nLabor for Repairs at any Facility, overtime working hours. (see SOW section I)\n1\nHR\n\n\n3006\nLabor for Repairs at any Facility, holiday working hours. (see SOW section I)\n1\nHR\n\n\n3007\nParts for Repairs at any Facility (see SOW section I)\n-\n-\n-\n-\nOPTION 4\n4001\nManhattan - Fire Alarm System\n4001AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n4001AB\nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n4002\nBrooklyn Fire Alarm System\n4002AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n4002AB \nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n4003\nSt. Albans Fire Alarm System\n4003AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n4003AB\nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n4004\nLabor for Repairs at any Facility, regular working hours. (see SOW section I) \n1\nHR\n\n\n4005\nLabor for Repairs at any Facility, overtime working hours. (see SOW section I)\n1\nHR\n\n\n4006\nLabor for Repairs at any Facility, holiday working hours. (see SOW section I)\n1\nHR\n\n\n4007\nParts for Repairs at any Facility (see SOW section I)\n-\n-\n-\n-\n\n"} Solicitation Number: 36C24226Q0191 Type: Combined Synopsis/Solicitation Base Type: Combined Synopsis/Solicitation NAICS: 561621 Classification Code: J063 Response Deadline: 2026-02-04T16:30:00-05:00 Office Address: ALBANY, NY Place of Performance: Brooklyn, New York, 11209 POC: Christopher Weider, Christopher.Weider@va.gov, (716) 862-7461 x22470 {"description":"The purpose of this amendment is to answer questions submitted by interested vendors. \n\nThe period for questions remains closed\n\nPlease see responses to vendor questions below: \n\nQuestion: What is the fire alarm device count by building for each location?\nAnswer: \nManhattan:\nBuilding #1 Main: 518 devices\nBuilding #2 Engineering: 7 devices\nBuilding #3 HR: 18 devices\nBuilding #5 AC Plant: 9 devices\nBuilding #6 OPC: 105 devices\n\nSt. Albans: \nBuilding #60 3 devices\nBuilding #64 10 devices\n*Building #65 11 devices\nBuilding #85 77 devices\nBuilding #86 75 devices\nBuilding #87 76 devices\nBuilding #88 76 devices\nBuilding #89 160 devices\nBuilding #91 55 devices\nBuilding #92 31 devices\nBuilding #93 30 devices\nBuilding #173 19 devices\nBuilding #176 5 devices \n\nBrooklyn: \nBuilding #1 Main: Engineering 659 devices\nBuilding#2 Domiciliary: 66 devices\nBuilding #4 Engineering:  33 devices\nBuilding #6 Chapel: 6 devices\nBuilding #8 Linear Accelerator: 1 device\nBuilding #14 Regional Counsel/Data Center: 18 devices\nBuilding #15 OPC: 195 devices\nBuilding #16 Daycare: 10 devices\n\nQuestion: What is the total number of buildings included at each campus?\nAnswer: \nManhattan: \n5 Buildings \n\nSt. Albans:\n13 buildings *including building #65 which is initially bypassed, See Section VI.A.3. of the Scope. \n\nBrooklyn: \n8 Buildings \n\n\nQuestion: What are the manufacturers and model numbers for all fire alarm control panels\nAnswer: \nManhattan:\nManufacturer: Notifier by Honeywell (ONYX Series)\nModel(s) Identified from Panel Labels:\nONYX NFS2-3030D / NFS2-3030ND\nONYX NFS2-640(E) / NFS-320SYS(E)\n\nSt. Albans:\nEdwards EST-3\n\nBrooklyn: \nManufacturer: Notifier Pittway Company\nModel(s) Identified from Panel Labels:\nAFP-400W/CBC \nAM2020/AFP1010/CBC\n#System 5000W/CBC\nManufacturer: Honeywell\nModel(s) Identified from Panel Labels:\nAFO 300/AFP 400 CBC\nNFS2-640(E) / NFS 320SYS(E)\nNFS2-3030D\n\nQuestion: Will existing fire alarm system AutoCAD (.dwg files) be provided to the contractor for updating the schematic diagrams or will these drawings be required to be created from scratch?\nAnswer: Existing fire alarm as built drawings are available and will be provided to the contractor in AutoCAD (.dwg) format and shall be used as a baseline. These drawings may not reflect current system conditions. The contractor shall field verify existing conditions and update the drawings to reflect the current fire alarm system configuration. Building floor plans may also be available in AutoCAD (.dwg) format for use in preparing the updated fire alarm drawings.\n\nQuestion: Can you please confirm the base scope of work does not require the contractor to install new printers?\nAnswer: The VA will provide printers. Contractor must install and test. \nPlease see updated Schedule below. Line Items 0001AC, 0002AC, and 0003AD have been added.\n\nLine Item\nDescription\nQuantity\nUnit of Measure\nUnit Price\nTotal Price\n0001\nManhattan - Fire Alarm System\n0001AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n0001AB\nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n0001AC \nPrinter Installation and Testing\n2\nEA\n\n\n0002\nBrooklyn Fire Alarm System\n0002AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n0002AB \nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n0002AC \nPrinter Installation and Testing\n1\nEA\n\n\n0003\nSt. Albans Fire Alarm System\n0003AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n0003AB\nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n0003AC\nSystem Upgrade to Replace Edwards EST-3\n1\nJB\n\n\n0003AD\nPrinter Installation and Testing\n1\nEA\n\n\n0004\nLabor for Repairs at any Facility, regular working hours. (see SOW section I) \n1\nHR\n\n\n0005\nLabor for Repairs at any Facility, overtime working hours. (see SOW section I)\n1\nHR\n\n\n0006\nLabor for Repairs at any Facility, holiday working hours. (see SOW section I)\n1\nHR\n\n\n0007\nParts for Repairs at any Facility (see SOW section I)\n-\n-\n-\n-\nOPTION 1\n1001\nManhattan - Fire Alarm System\n1001AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n1001AB\nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n1002\nBrooklyn Fire Alarm System\n1002AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n1002AB \nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n1003\nSt. Albans Fire Alarm System\n1003AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n1003AB\nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n1004\nLabor for Repairs at any Facility, regular working hours. (see SOW section I) \n1\nHR\n\n\n1005\nLabor for Repairs at any Facility, overtime working hours. (see SOW section I)\n1\nHR\n\n\n1006\nLabor for Repairs at any Facility, holiday working hours. (see SOW section I)\n1\nHR\n\n\n1007\nParts for Repairs at any Facility (see SOW section I)\n-\n-\n-\n-\nOPTION 2\n2001\nManhattan - Fire Alarm System\n2001AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n2001AB\nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n2002\nBrooklyn Fire Alarm System\n2002AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n2002AB \nSemi-Annual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n2003\nSt. Albans Fire Alarm System\n2003AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n2003AB\nSemi-Annual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n2004\nLabor for Repairs at any Facility, regular working hours. (see SOW section I) \n1\nHR\n\n\n2005\nLabor for Repairs at any Facility, overtime working hours. (see SOW section I)\n1\nHR\n\n\n2006\nLabor for Repairs at any Facility, holiday working hours. (see SOW section I)\n1\nHR\n\n\n2007\nParts for Repairs at any Facility (see SOW section I)\n-\n-\n-\n-\nOPTION 3\n3001\nManhattan - Fire Alarm System\n3001AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n3001AB\nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n3002\nBrooklyn Fire Alarm System\n3002AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n3002AB \nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n3003\nSt. Albans Fire Alarm System\n3003AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n3003AB\nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n3004\nLabor for Repairs at any Facility, regular working hours. (see SOW section I) \n1\nHR\n\n\n3005\nLabor for Repairs at any Facility, overtime working hours. (see SOW section I)\n1\nHR\n\n\n3006\nLabor for Repairs at any Facility, holiday working hours. (see SOW section I)\n1\nHR\n\n\n3007\nParts for Repairs at any Facility (see SOW section I)\n-\n-\n-\n-\nOPTION 4\n4001\nManhattan - Fire Alarm System\n4001AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n4001AB\nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n4002\nBrooklyn Fire Alarm System\n4002AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n4002AB \nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n4003\nSt. Albans Fire Alarm System\n4003AA\nAnnual Fire Alarm System Maintenance and Inspection\n1\nEA\n\n\n4003AB\nSemi-Annual Fire Alarm\nSystem Maintenance and\nInspection\n1\nEA\n\n\n4004\nLabor for Repairs at any Facility, regular working hours. (see SOW section I) \n1\nHR\n\n\n4005\nLabor for Repairs at any Facility, overtime working hours. (see SOW section I)\n1\nHR\n\n\n4006\nLabor for Repairs at any Facility, holiday working hours. (see SOW section I)\n1\nHR\n\n\n4007\nParts for Repairs at any Facility (see SOW section I)\n-\n-\n-\n-\n\n"}
Get tenders like this in one daily alert
Use this notice as context when Tenqual drafts your search scope and fit criteria.